Water heaters · Recovery

How long does a water heater take to reheat

Heating a whole cold tank and waiting after a shower are different situations. A cold-tank estimate starts with all the stored water at one assumed temperature. After ordinary use, some water may still be hot and the heater may already have replaced part of the heat used.

This guide shows how to estimate a cold tank's heating time with a worked example, then explains what to ask about your own after-use routine. The calculation does not tell you when another full shower will be ready: some hot water can return before the whole tank has recovered.

On this page (6)

Decide what you are timing

  • Cold tank to a stated target: estimate the heat needed by the entire actual stored volume. This describes a thermal starting condition, not instructions to fill or start a newly installed heater.
  • Recovery after use: cold supply water replaces the hot water drawn from a normal pressurized storage tank. The tank normally remains water-filled while this happens: the thermal recovery wait is not a separate wait for the tank to refill. The tank may still contain warm or hot water, and heating may already have occurred during the draw. A shower therefore does not necessarily leave a whole tank of cold water to heat.
  • Enough useful hot water: define the desired outlet temperature, flow and duration. A warm first few seconds at a tap does not establish enough stored heat for a full shower. Layering inside the tank, mixing and subsequent cold-water entry matter.
  • Hot water reaching a distant faucet: cooled water in distribution pipes creates delivery delay even when the tank is already hot. That is not tank recovery. See tank versus tankless.

Was the cylinder or tank physically emptied? That is a refill and readiness check, not a recovery-time estimate. Start with the restoration checks; for a documented storage heater, check the model’s filling, air-purge and leak-check instructions before heating. Do not time recovery from when utility service returned if the equipment was not ready to heat.

Worked example for a whole cold tank

First, find the heater's recovery rate: the amount of water it can heat in an hour through a stated temperature increase. For example, “21 US gallons per hour at a 90°F rise” describes heating capacity. The 90°F is a temperature difference, not a thermostat setting.

Here is a hypothetical cold-full scenario using A. O. Smith's March 2025 ENT-50 specification:

  • Water volume: 46 US gallons, the rated storage volume in that sheet.
  • Starting water: all of it uniformly at 50°F.
  • Target water: 120°F, so the required increase is 70°F.
  • Recovery rating: 21 US gallons per hour at a 90°F rise.
  • During heating: no further hot-water use; normal heating at approximately constant effective output matching that rating.

With those conditions, the calculated heat-replacement time is about 102 minutes — roughly 1 hour 42 minutes. The temperatures are calculation assumptions, not advice to change a setting.

How to calculate it

Estimated minutes = 60 × volume in US gallons ÷ rated recovery GPH × actual temperature rise ÷ rated temperature rise.

For the example above:

60 × 46 ÷ 21 × (120 − 50) ÷ 90 = about 102 minutes.

Use the same temperature-difference unit for both rises. With Fahrenheit inputs, actual rise = target °F − initial °F. This is an energy-balance estimate derived from the recovery rating, assuming the rating applies to the configuration and effective output stays approximately constant across the temperature interval.

If that same hypothetical water volume were uniformly at 90°F instead, only a 30°F rise would remain: 60 × 46 ÷ 21 × 30 ÷ 90 = about 44 minutes. A real tank after a shower is normally not uniformly at one temperature; a single outlet-temperature reading cannot establish this starting condition.

What the estimate means: it estimates heat replacement, not a manufacturer's tested elapsed time or a guaranteed wait for your heater. Heat losses, control delays and cycling, layering of hot and cooler water inside the tank, and the manufacturer's definition of completed recovery can change actual time. Further hot-water use adds heating load. The result is not a fault deadline.

Do not substitute first-hour rating

First-hour rating answers a different question: how much hot water a storage heater delivers in an hour beginning fully heated under the rating test. It includes the starting reserve and is not an empty-to-hot timer or a repeatable allowance for every later hour.

The cited ENT-50 sheet separately lists nominal capacity of 50 gallons, rated storage volume of 46 gallons, 62 gallons first-hour delivery, and 21 GPH recovery at a 90°F rise. Do not divide a tank volume by 62 to calculate cold-tank reheating. Do not assume the nominal gallon label equals actual stored volume. Match the specification revision and installed configuration.

Gas, conventional electric and heat-pump tanks differ

Gas storage: use the matching model's recovery performance, not burner input alone. Input BTU/h is not the same as heat delivered to water. An A. O. Smith GCR-50 sheet lists 48 gallons rated storage and 43 GPH at a 90°F rise. Applying the same illustrative 50°F-to-120°F, no-draw calculation gives about 52 minutes. That is a conditional calculation from the cited December 2019 specification, not a guarantee for every GCR-50 series or every gas tank.

Conventional electric storage: use documented recovery for the actual voltage, wattage and element-control arrangement. Two listed elements do not automatically mean both heat simultaneously; adding their nameplate wattages can produce the wrong estimate. Prefer the applicable recovery figure rather than inferring output from element count. Bradford White explicitly distinguishes one-element-at-a-time and simultaneous arrangements in its service reference; this is a configuration distinction, not permission to change wiring.

Heat-pump storage: the selected mode and surrounding air affect performance. Resistance backup can change the heating output during recovery. Rheem's ProTerra explanation describes different heat-pump, hybrid and electric behavior; it is not a universal timing chart for all heat-pump heaters. An electrical input wattage is not the heat pump's thermal output, and a conventional-electric recovery number cannot simply be carried over to compressor-only operation. Use a model- and mode-specific recovery or heat-up table at relevant air and water conditions for a more precise estimate. This is not advice to switch modes.

Tankless: a conventional tankless unit does not wait to reheat a large stored reserve. Its ability to supply the requested flow and temperature, plus delivery through the pipes, is a different question. See tankless sizing.

Choose the next step that matches your question

Planning a cold-full heating scenario: use the actual rated storage volume and applicable recovery rate, then state an assumed starting-water temperature and target temperature. Use the worked example above as the pattern, keeping its assumptions separate from observations of your own tank. Do not change a thermostat or drain a tank to reproduce the example.

Waiting after ordinary use or planning another shower: record the accessible exact model, the current operating mode if already known, shower lengths and flow rates if known, time between draws, and other hot-water uses that overlap. These are useful observations; you do not need to measure temperatures inside the tank or calculate a remaining heat deficit. Give that routine to the manufacturer or installer and ask for applicable recovery or consecutive-draw performance for the model, mode and relevant incoming-water and room conditions. A cold-full calculation alone cannot establish when another complete shower will be ready. If there is no applicable performance information, that specific wait remains unknown rather than becoming a generic 30-, 60- or 90-minute promise.

Read only accessible exterior labels and normal user displays; do not remove covers or test exposed wiring to collect information. For an appliance you do not control, report the routine and symptoms to the building manager instead of operating it.

If recovery is newly worse under the same routine, all hot outlets remain cold, or a warning or error is present, use the not-heating guide rather than repeatedly extending a guessed wait. This article does not provide reset, relighting, refill or thermostat-adjustment instructions.