What the common modes actually do
Continuous
Ventilation runs continuously at the selected speed. “Low” on a controller is not a measured outdoor-air rate.
Boost / high
A temporary increase for moisture or other short-term needs. A timer may return the unit to its normal mode after the boost ends.
Intermittent
Alternates ventilation with another state. On some Lifebreath controls, 20/40 means 20 minutes of ventilation and 40 minutes of standby; on others, the second period is recirculation.
Recirculation
Moves indoor air without bringing in outdoor air during that part of the cycle. It is not equivalent to fresh-air ventilation.
Humidity control
A dehumidistat can call for more ventilation, but its effect depends on the moisture difference outdoors and indoors. Model-specific overrides may take priority over the mode you selected.
Defrost
An automatic protective sequence, not a homeowner-selected daily run schedule. Do not disable it to keep a fan running.
Source: Lifebreath: residential HRV owner’s manual (2025); Health Canada: ventilation and the indoor environment.
Winter moisture: damp and dry need different checks
If windows are wet: record the indoor relative humidity (RH), outdoor temperature and time of day. Use working kitchen and bathroom exhaust as intended and check obvious moisture sources. Confirm the HRV is operating in its specified ventilation mode and that filters and accessible outdoor hoods are not obstructed. Persistent condensation is a reason to investigate, not proof that a higher fan speed is the only fix.
If rooms are too dry: excessive ventilation can contribute, but do not turn off a required ventilation system as the default solution. Check whether a humidity override or boost is running longer than intended. Ask the installer to confirm the commissioned rate and permitted control options before reducing ventilation.
There is no single winter RH setting that prevents condensation in every home. Outdoor temperature, glazing, cold surfaces, moisture generation and the ventilation rate all matter. A low outdoor relative-humidity reading is not a reliable comparison with indoor RH unless temperature is considered.
Source: Health Canada: ventilation and the indoor environment; Lifebreath: residential HRV owner’s manual (2025).
Should the HRV be off in summer?
Do not turn it off simply because the calendar says summer. The house still needs a ventilation plan. But humid outdoor air can add moisture, and a humidity control that helps in winter may behave differently in summer.
Check the controller’s seasonal instructions and any automatic humidity-control disable. Follow local outdoor-air advisories during wildfire smoke or other pollution events; use the equipment and public-health guidance for the actual situation. An ERV can limit some incoming moisture, but cooling or dehumidification may still be needed.
Source: Health Canada: ventilation and the indoor environment; Lifebreath: residential HRV owner’s manual (2025).
Why does it stop, change speed or seem to recirculate?
First read the display and controller manual. A timed boost, humidity call, intermittent mode or automatic defrost may explain the change. “Fan running” does not by itself confirm outdoor-air ventilation.
Note the mode, any fault code, the outdoor temperature and whether the unit returns to normal afterward. Recurring faults, persistent ice, unusual noise or inadequate airflow after permitted maintenance call for service. Do not move balancing dampers, bypass sensors or open electrical enclosures to force continuous operation.
The bathroom timer says 20/40/60. Is that the same as 20/40 on the main control?
No: confirm which control you are reading. On the Lifebreath 99-DXPL02/99-DXPL03 main controls, 20/40 is an hourly pattern: 20 minutes of ventilation and 40 minutes either off or recirculating, depending on the selected mode and the equipment. The matching Lifebreath 99-DET01 or 99-DET02 auxiliary timer instead calls for a single high-speed ventilation period of 20, 40 or 60 minutes. The residential manual, pp. 10–13, explains both controls and warns that a timer generally will not operate while the main mode is set to OFF unless specifically installed to do so. Do not interpret timer override as permission to leave the main control off.
- It gets louder after a shower, then returns to its previous setting: If you have confirmed that the bathroom button is an HRV/ERV boost and its boost light was on, that sequence fits a temporary override. For example, on a supported Lifebreath setup a 20-minute boost ends by returning to the selected mode and speed; it does not turn the recurring 20/40 schedule into 20 minutes per hour of high speed. A separate bathroom exhaust-fan timer is not proof that the HRV boosted.
- The timer lights up, but you do not notice a change: Note the exact model of the main control and timer, what the main display says while the timer is lit, and what happens when it expires. If the main control says OFF, was already on high, or the button serves a separate fan, the light alone does not tell you how much outdoor air reaches the rooms. Ask the installer to identify what that switch controls rather than opening the wall plate, resetting the system or changing the normal setting.
- The fan runs during the other 40 minutes: On some systems that is recirculation, not outdoor-air ventilation. Check the main control’s mode icon and manual. For example, the Broan Déco-Touch 40600 can be programmed for OFF or recirculation in the non-exchange part of an intermittent cycle when supported by the unit. The Broan VBATHW is a different example of a short boost timer, specified for compatible AI Series HRV/ERV and ONE Series ERV systems; appearance or the same numbers do not establish compatibility.
Keep the normal operating setting specified for your home. If a boost does not end as expected, write down the controller and timer model, main mode, timer indication, humidity-override indication if shown and when the change started. That helps distinguish an active override from a fault; it does not replace testing the installed airflow.
Source: Lifebreath: residential HRV owner’s manual (2025); Fantech: VER150 installation and operation manual; Broan: ERV70 / HRV80 / HRV90 owner’s manual.
Does the furnace or heat-pump blower have to run?
It depends on the duct and control arrangement. Some installations distribute ventilation air through dedicated ducts; others use the forced-air system and need coordinated blower operation. Replacing a furnace with a heat pump can change that arrangement.
Ask the installer: “How does outdoor air reach the rooms when the heating or cooling call is off, and what interlock does this installation require?” Get the answer for your layout rather than leaving the blower on permanently based on a generic internet rule.
Source: Fantech: VER150 installation and operation manual; DOE / PNNL: balanced HRV/ERV commissioning checklist.
Make a short operating record
Use this before a service conversation or after a permitted setting change. Record what you observed, not a guessed airflow. Entries stay in this page and are lost when it is closed or reloaded.
HRV operating record
Your record
Sources and scope
Read the sources and limits
Checked November 9, 2026. General guidance for English-speaking homeowners; the exact equipment manual and local requirements govern an individual system. Manufacturer examples apply only to the named models.
- Health Canada: ventilation and the indoor environment
- Lifebreath: residential HRV owner’s manual (2025)
- Fantech: VER150 installation and operation manual
- Broan: ERV70 / HRV80 / HRV90 owner’s manual
- DOE / PNNL: balanced HRV/ERV commissioning checklist
The illustrations are original explanatory schematics, not installation drawings. No claim of measured performance, code compliance, or universal operating settings is made for your home.