Compare the two proposals in six checks
Both HRVs and ERVs recover heat during ventilation. An ERV also transfers some moisture between the air streams; an HRV does not intentionally provide that moisture-transfer function. That distinction explains the comparison. It does not make either category the best choice for every house in a state or climate zone.
Use the same six checks on each quote. The type mainly changes how the ventilator handles moisture. The exact model and installation determine whether it can meet the rest of the job.
- Humidity
- An HRV transfers heat; an ERV transfers heat and some moisture. Consider which direction you want moisture to move and when.
- Outdoor air delivered
- Ask for the intended airflow setting and measured supply and exhaust flows after installation. A fan’s maximum rating is not the delivered outdoor airflow.
- Certified recovery
- Look up the exact models. Compare the same measure at equivalent net airflow, test temperatures and humidity.
- Defrost
- Check how the exact model protects against frost and what happens to outdoor airflow and supply–exhaust balance during defrost.
- Duct fit
- Have the installer show where the air goes, which ducts are used and whether a central fan must run for that design.
- Upkeep
- Check space to remove filters and the core, the matching care instructions and whether a condensate drain needs attention.
Compare the moisture you want to keep or remove
| Situation | Comparison |
|---|---|
| Hot, humid outdoors; cooler, drier indoors | An ERV can limit incoming moisture, without eliminating the conditioning load. |
| Cold season; indoor air is already too dry | An ERV can retain some moisture. |
| Cold season; a tight, highly occupied home stays too humid | An HRV may better match moisture removal. |
Seasonal tradeoffs can change. Location alone does not settle the question.
Illustrative comparison: two homes in one town can have opposing goals: retain moisture in dry winter rooms, or reduce excessive indoor moisture. That changes which approach deserves consideration. This example is not a diagnosis or model recommendation.
Separate delivered outdoor air from the recovery rating
Outdoor airflow: look for a rating and a measured result
Net supply in the HVI test subtracts measured cross-leakage from the gross supply airflow under stated test conditions. Ask for the model’s net supply at a relevant airflow setting and duct pressure. Then have the installer measure the installed ventilation rate, document both supply and exhaust at the planned operating setting, and check that the airflow reaches the intended rooms. The test rating and the installed measurement are different checks.
Worked example: Two proposals show 75 and 85 cfm net supply in their lab listings. Neither figure proves the system will deliver the project’s planned 70 cfm after installation. If the commissioning record shows 62 cfm of outdoor supply at the planned setting, ask the installer to account for that shortfall and document the corrected supply and exhaust readings. These numbers illustrate the comparison, not a ventilation requirement for your home.
Recovery: compare like with like
Use the same metric at comparable net airflow and indoor and outdoor test conditions. HVI distinguishes sensible recovery efficiency (SRE) from adjusted sensible recovery efficiency (ASRE): standard SRE includes the equipment’s electrical consumption; ASRE is for calculations that enter fan power separately. If comparing total recovery ratings, which include moisture or latent energy transfer, also match the named metric and conditions. A higher percentage measured or calculated differently does not settle the choice.
Ask the installer to show the exact model’s entry in the HVI Certified Products Directory. It gives tested airflow and recovery performance; it does not show whether a particular installation supplies every room as intended.
Check defrost, duct fit and upkeep
Defrost: ask what happens to ventilation
Ask how the exact model protects its core where you live, whether defrost changes outdoor airflow or supply–exhaust balance, and whether any accessory is required. Check power use and normal controls as well as winter operation. HVI describes optional very-low-temperature testing; if those test results are listed, use them alongside the model instructions. A normal recovery rating does not describe every defrost cycle.
Duct fit: ask to see the air path
Establish whether the proposal uses dedicated ducts or connects to existing forced-air equipment. Have the installer show where outdoor air is supplied, where indoor air is picked up, and what happens when the central fan is off. DOE’s existing-home guidance (§8.1, figure 17) shows why some shared-duct layouts behave differently when the central fan is stopped.
Upkeep: check access before buying
Check how you will reach the filters, core, exterior hoods and any condensate drain. Confirm the exact care instructions before buying. The Broan example cited in the companion explanation gives different treatment for heat-recovery and energy-recovery cores. Never transfer one model’s cleaning, control or defrost instructions to another merely because both are called ERVs or HRVs.
In the US, applicable requirements depend on the jurisdiction and adopted rules. HVI’s code fact sheets expressly warn that local adoption can include amendments. In Canada, requirements likewise need an address-specific provincial or territorial and municipal check; do not apply a U.S. code fact sheet as Canadian approval. A general comparison article is not a permit check, ventilation-rate calculation or approval to alter ducts or electrical equipment.
What to ask before choosing
If the choice is still unclear, start with: “What moisture problem are we trying to solve?” Describe when rooms feel dry or damp and any humidity readings you already have. Ask the installer:
- Why does the proposed HRV or ERV suit that problem, using the tradeoffs above?
- How much outdoor air will it deliver, and do the competing ratings use matching test conditions?
- What is still unknown—such as the moisture source, duct arrangement or winter operation—and what check would settle it?
If the proposals still sound interchangeable, ask for that explanation before committing to one.
Whichever approach is considered, ventilation is only part of indoor-air management. Reducing the pollutant source and using appropriate filtration remain distinct measures; outdoor-air quality also needs consideration. Do not treat this equipment comparison as a health guarantee or a substitute for investigating a hazardous source.
Sources and limits
Show SourcesHide Sources
Reference links checked November 16, 2026. This comparison covers U.S. and Canadian homes; verify local installation requirements separately.
- U.S. Department of Energy: energy recovery ventilation; DOE Building America: selecting ventilation systems for existing homes (§8.1 and §8.2, humidity, equipment and duct configurations).
- Home Ventilating Institute: Certified Products Directory, Section III, energy and airflow definitions, buying guide, SRE/ASRE and related metrics, and U.S. code fact sheets.
- Pacific Northwest National Laboratory: balanced HRV/ERV installation and commissioning checklist.
- Natural Resources Canada: certified HRVs and ERVs and ventilation system maintenance.
- U.S. EPA: sources, outdoor air, ventilation and filtration.
- Broan ERV70 / HRV80 / HRV90 owner’s manual, p. 7 (model-specific core care).